Rooftop Tray PM reference PDF ↓

Sheet E-200 · Grounding & bonding

Grounding and bonding the rooftop tray

The tray sits on PVC and rubber sleepers, so it is electrically floating until someone bonds it. ANDREW publishes no grounding detail for this line, so the grounding design comes from the NEC, the site's lightning protection and the owner's or carrier's grounding standard. This page covers the full scope: what to bond, with what, in what order, how to test it, and what to ask before you buy.

The solution in eight lines

  1. Make the tray continuous: a bonding jumper across every splice joint and every hinge.
  2. Bond the tray to ground at both ends, at the roof ring ground, the lightning-protection conductor or the entry ground bar, using the owner standard's conductor (commonly #2 AWG tinned solid copper).
  3. Bond the step-over (RT-ST) and the hood entry (MT-365G), plus any metal within the bonding distance of a lightning-protection conductor (7 ft in AT&T's practice).
  4. Ground every coax shield with an ANDREW SureGround kit at the antenna end and at the entry ground bar, plus at the top and bottom of vertical drops if the standard requires it.
  5. Bond the entry ground bar to the building's grounding electrode system. The electrical contractor makes this connection.
  6. Use rooftop-safe connections: two-hole compression lugs, tinned copper, stainless hardware and antioxidant compound. No exothermic welds on a roof.
  7. Never drill or cut the tray to land a lug without ANDREW's written OK. Use listed tray clamps or the approved bolt location.
  8. Test, photograph and record every bond before the covers go on, then hand over an as-built grounding drawing.
① ① ② ② ③ kit ④ kit ⑤ bar ⑥ ROOF RING / LPS CONDUCTOR BLDG ANTENNA
① jumper across every splice (and every hinge) · ② bond each tray end to the roof ground conductor · ③ coax ground kit at the antenna end · ④ ground kit at the entry · ⑤ entry ground bar on the hood entry · ⑥ to the building grounding electrode system. This is a schematic, not to scale. The site grounding drawing governs.

Which rules govern

Follow the strictest one that applies
SourceWhat it controls here
NEC (NFPA 70), 2023 edition in San Antonio392.60(A): metal tray that carries only non-power cable must be electrically continuous, through approved connections or a bonding jumper no smaller than 10 AWG. That language dates from the 2017 edition. Check the adopted text. Article 250 covers bonding methods, and Articles 800/810/820 cover coax shields, antenna masts and the bond at the building entrance.
NFPA 780 / UL 96ALightning protection. Metal within the calculated bonding distance of a lightning-protection conductor gets bonded to it, using listed fittings. If the building has a certified system, have the lightning-protection contractor make those bonds so the certification holds.
Owner / carrier standardUsually the strictest, and it sets conductor sizes, connector types, kit locations and acceptance tests. Examples: AT&T ATT-TP-76416, Motorola R56, ANSI/TIA-607. Get the one for this site in writing before you buy.
ANDREW SureGround bulletin 7598195How to install the coax ground kits: stripping tool per size, 8 in (203 mm) minimum lead bend radius, and no installation in the presence of thunderstorms.
ANDREW Limited Warranty §8(g)Drilling or cutting the tray for a lug is a modification. Get written authorization first (exclusions).

A site under the exclusive control of a communications utility can fall outside the NEC's scope (NEC 90.2). The building owner, the carrier's standard and the AHJ still apply. Never treat "not NEC" as "not grounded."

1. Make the tray electrically continuous

2. Bond the tray to the site ground

3. Ground the coax shields

ANDREW SureGround kits (bulletin 7598195 rev E)
CableKit part numbersStrip tool
1/2 inSG12-06B2A · SG12-12B2UGKT-L4SG
7/8 inSG78-06B2A · SG78-12B2UGKT-78SG
1-1/4 inSG114-06B2A · SG114-12B2UGKT-114SG
1-5/8 inSG158-06B2A · SG158-12B2UGKT-158SG

4. Entry ground bar to building ground

5. Materials and connections

ItemUseWhy
ConductorTinned solid copper. #2 AWG is common for bonds to the ring, with #6 AWG the minimum for unit bonds (AT&T). Use stranded only for flexible jumpers.Tin keeps copper from attacking the zinc on the galvanized tray
ConnectorsTwo-hole compression lugs with a hydraulic crimp, or listed (UL 467) tray grounding clampsTwo holes won't rotate loose. Clamps avoid drilling the tray.
HardwareStainless bolts, flat washers and external-tooth lock washersCorrosion, and a bite through the coating
CompoundAntioxidant on every mechanical jointKeeps moisture out of the contact
Touch-upZinc-rich coating (ASTM A780) wherever the galvanizing is disturbedProtects the coating, and the tray warranty
Not on a roofExothermic (Cadweld-type) weldsAT&T calls them a fire hazard on rooftops, and they burn off the galvanizing. Use compression instead.

6. Routing on a non-penetrating roof

7. Grounding bill of materials

The estimator counts these items automatically for a straight run, using the conservative default:

ItemCount
Bonding jumpers across joints1 per splice joint (sections − 1, per tray)
Hinge jumpers1 per extension kit
Tray-to-ground bonds2 per tray, plus 1 per lightning-protection crossing within the bonding distance
Step-over / hood entry bonds1 each
Two-hole lugs2 per conductor
Coax ground kitsAt least 2 per installed cable, sized to the cable (more if the standard asks)
Entry ground bar1 per entry, with enough holes for every kit plus spares
ConductorMeasure from the grounding drawing and add 10% for routing
ConsumablesAntioxidant, stainless hardware, zinc-rich touch-up, kit tape

Example: six coax cables on an 8-run tray, 60 ft straight. That's 8 sections and 7 splices, so 7 jumpers, 2 end bonds, 18 lugs and 12 ground kits, plus the entry bar and the conductor.

8. Testing, inspection and closeout

9. Texas and San Antonio

10. Questions to settle before ordering

Sources