Sheet I-200 · Turns & elevation changes
Making 90° turns and elevation changes
ANDREW makes no 90° corner or elbow for the rooftop bridge line. The adjustable splices make the turn: each one bends from 0 to 45°, so a 90° takes two of them with a straight section between. None of these parts come in the bridge kits. Order them separately.
The short answer
- Horizontal 90°: two adjustable splices, each set to 45°, with one full 8 ft section between them as the diagonal leg. Use MT-F1573-11 for 4-run, MT-F1574 for 8-run and MT-F1597 for 12-run trays.
- Up or down (curbs, parapets, roof steps): the hinged extension kits, which adjust vertically from 0 to 45°. Use MT-F1703 for 4-run and MT-F1704 for 8-run trays. The line has no 12-run extension.
- In the kit: the 8 ft bridge section, its hardware and three sleepers. That's all.
- Not in the kit: splices (not even for straight joints), extension kits, step-overs, hood entries and protection pads.
The distributor listing (Talley) states the 0–45° ranges. ANDREW's own spec sheets give only dimensions and don't describe the function. The two-splice method is the program's reading of those ranges, not an ANDREW detail. Confirm it against the assembly drawing (RFI 11).
What's in the box and what you order separately
| Item | In the kit? | Order |
|---|---|---|
| 8 ft (96 in) bridge section with cover | Yes | 1 per kit |
| Assembly hardware | Yes | — |
| Sleepers | Yes, 3 | Spares if the roof manufacturer wants closer spacing |
| Adjustable splice, straight joint | No | 1 per joint between sections, to be safe. Some distributor BOMs describe kit components as "self splicing", so ask whether straight joints need one (RFI 11). |
| Adjustable splice, turn | No | 1 per 45° of turn (2 per 90°). A quote that lists only bridge kits can't make a turn. |
| Hinged extension kit (vertical change) | No | 1 per change in elevation, 4- and 8-run only |
| Protection pad / mat under sleepers | No | CT-P4 or MT-F1637, 1 per sleeper if the roof requires it |
Talley lists the splices as special order and non-returnable. Count them carefully the first time, because you can't send extras back.
Horizontal turns
- Turn angle → splices at the turn: one splice per 45° or less. A 30° or 45° jog takes 1, a 90° takes 2, and a 135° takes 3, each with a full section between splices.
- Each straight leg ends at a joint, so it has to be a whole number of 8 ft sections unless ANDREW authorizes a field cut in writing (warranty §8(g)). Round each leg up separately.
- Tees and crosses: no tee or cross part is listed for the rooftop bridge line. If the design branches, send the question to ANDREW before you draw it (RFI 11).
- Don't substitute ladder-tray fittings. CommScope / Cope 90° covers and fittings (the LDRLT-V90, VRI90/VRO90 and VTJ series) belong to a different ladder-tray system and aren't listed as compatible with the bridge kits.
Can two 45° splices go back to back?
Not as a designed assembly. Plan on a section between them. The outline drawing shows what the splice is: a flat 45° wedge plate, not a piece of tray. One section end bolts through fixed 7/16 in holes along one straight edge. The other section end bolts through curved slots, which is what lets it swing from 0 to 45°. The plate joins two channel ends, so:
- Stack two plates and the second plate's fixed edge has no channel to bolt to. The slots are laid out for a section's end, not for another plate.
- The full 90° would happen over one plate's footprint (about 33 in on the 12-run). The inside cables would bend far tighter than across two turns 8 ft apart, and the corner would have no channel or cover over it.
- The designed fix for a tight corner is a shorter diagonal, not a stacked plate. That means cutting a section, which needs ANDREW's written authorization (warranty §8(g)). Get it, along with the minimum diagonal length, the hole pattern to drill in the cut end and the touch-up method (zinc-rich coating to ASTM A780), and make sure at least one sleeper still bears under the short piece (RFI 11).
- If ANDREW approves a back-to-back detail in writing, follow their drawing. Until then, don't improvise an adapter plate. A fabricated part is a modification too.
Protecting the cable through a turn
| Cable | Single bend | Repeated bends |
|---|---|---|
| 1/2 in (LDF4-50A) | 2 in | 5 in |
| 7/8 in (LDF5-50A) | — | 10 in (older listing) |
| 1-5/8 in (LDF7-50A, now AVA7-50) | 8 in | 20 in |
Use the datasheet for the exact cable on your BOM. Other families (AVA, superflexible jumpers, hybrid fiber/power) have their own figures.
- Let the cable sweep, not kink. Spread the 45° across the whole plate so the bend starts before the joint and finishes after it. Never bend a cable over the end of the channel or the edge of the plate.
- Put the biggest cables on the outside of the turn. The inside position has the tightest radius, so give it to the smallest cable.
- Pad every edge the cable can touch. Fit UV-rated edge guard or grommet strip on channel ends, plate edges and the curved slots. Sheared galvanized edges cut jackets when the roof heats and cools every day.
- Support both sides of the turn. Snap-in hangers in the kit holes as close to the joint as the hole pattern allows, at the cable maker's hanger spacing. No cable should hang unsupported across the gap.
- Leave slack, don't pull tight. Coax grows and shrinks with roof temperature (a dark membrane can pass 150 °F in a San Antonio summer). A cable pulled tight against the inside of a turn saws itself on the edge. Leave an easy, supported curve.
- No tight zip ties on coax. Use the hanger system. If ties are allowed at all, they must be UV-rated, snug and never crush the corrugation.
- Cover the turn. The splice plate has no lid, so the cables at a turn are exposed to UV, hail and boots. Ask ANDREW what covers a turn. Until then, keep turns out of walk paths, flag them, and use protection the roofing manufacturer accepts.
- Keep connectors, ground kits and splices off the bend. Land ground kits on straight runs.
- Inspect turns first after every hail or high-wind event. Look for jacket scuffs at the edges, crushed hangers and shifted sleepers.
Elevation changes
- Use a hinged extension kit (MT-F1703 for 4-run, MT-F1704 for 8-run). Each one hinges from 0 to 45° vertically to take the tray up or down a curb, parapet or roof step.
- MT-F1703's function comes from the distributor listing (12 in W × 24 in L, 0–45° vertical, hinged). MT-F1704's is inferred from its sibling and the matching envelope, because no listing was available for it. Confirm before you order (RFI 3).
- The 12-run bridge (MT-F1595) has no extension kit. Route a 12-run tray around level changes, split it into a 4-run and an 8-run tray at that point, or get ANDREW's solution in writing.
- Check the cable's minimum bend radius at every hinge, and remember that a sloped section carries its dead load onto fewer sleepers.
- Crossing a walkway is a different problem: the RT-ST step-over lets people climb over the tray. It doesn't carry the tray over an obstruction.
SnapStak cover kits
The RT-CB4D / RT-CB8D / RT-CB12D cover kits don't list any splice, turn or extension part. Their sheets don't say how sections are joined, turned or raised. Don't plan a cover-kit route with turns until ANDREW answers RFI 6.
Adding turns to the estimate
- Break the route into straight legs at every turn and every elevation change.
- Run the estimator once per leg. It rounds each leg to whole sections and counts that leg's internal joints.
- Add, for each 90° turn, 2 splices + 1 bridge kit (the diagonal). For each 45° jog, add 1 splice.
- For each elevation change on a 4- or 8-run tray, add 1 extension kit, plus a splice for each joint the hinge creates, as the assembly drawing shows.
- Add the weight of the extra kits to the dead load the engineer checks.
Example: an L-shaped 8-run route with legs of 40 ft and 24 ft. Leg A is 5 sections with 4 splices; leg B is 3 sections with 2 splices. The 90° adds 1 diagonal kit and 2 splices. The total is 9 × MT-F1543 and 8 × MT-F1574.
Where this comes from
- Talley (ANDREW distributor), coax-support category and product listings: MT-F1573-11 and MT-F1574 ("Horizontal Adj Splice Plate, 0-45 Deg"), plus the category list for MT-F1597 and MT-F1703 ("0-45 Deg Vert Adj Hinged Coax Bridge Ext Kit"). Retrieved 2026-10-27.
- ANDREW spec sheets for the bridge kits (contents: section, hardware, 3 sleepers). See Sources.